Code:
EN54C-3A17LCD(v. 1.2)
Name:EN54C 27,6V/3A/2x17Ah/LCD power supply for fire alarm systems
| Power supply output |
3 A / 27.6 V DC / 85.2 W - for intermittent operation – Imax b (5min) 2.2 A / 27.6 V DC - for continuous operation – Imax a |
| Standards |
Certification with Fire protection standard EN54-4 Certification with Smoke extraction and ventilation standard EN12101-10 Certificate of constancy of performance CNBOP-PIB No 1438-CPR-0628 Certificate of approval CNBOP-PIB No. 5222/2024 |
| Battery charging current | 0.8A |
| Battery | 2 x 17Ah |
| Current consumption by PSU systems | 64mA max. |
| Efficiency | 89% |
| Dimensions |
385 x 402 x 88 [+/-2 mm] distance from surface: 8 mm |
| Protections |
SCP, OLP, OVP, UVP, tamper – opening of enclosure |
| Technical outputs relay type |
EPS – AC power failure ALARM – collective failure |
| Technical input | EXTi – external failure |
| Closing | Key lock |
| Installation | surface-mounted |
| Indication | LCD display |
| Material |
steel DC01, 1mm, RAL3001 (red), metallic |
| Protection grade EN60529 | IP 30 |
| Warranty | 3 years |
| Notes |
- remote monitoring, option: LAN, RS485 (appropriate modules required) |
Intended use
Documents
Software
Accessories
-
HPB18-12 - 18Ah/12V HPB battery
-
EN54C-LB4 - LB4/0,5A/FTA fuse module EN54C
-
EN54C-LB8 - LB8/0,5A/FTA fuse module EN54C
-
EN54C-LS4 - EN54C-LS4 sequential module for actuators without return spring
-
EN54C-LS8 - EN54C-LS8 sequential module for actuators with return spring
-
INTE-C - Interface ETHERNET
-
INTR-C - Interface RS485-TTL
-
INTRE-C - Interfaces RS485-ETHERNET
-
AWOP/AWOZ - Fire protection installation boxes
Related products
-
EN54C-5A17LCD - EN54C 27,6V/5A/2x17Ah/LCD power supply for fire alarm systems -
EN54C-5A40LCD - EN54C 27,6V/5A/2x40Ah/LCD power supply for fire alarm systems -
EN54C-10A17LCD - EN54C 27,6V/10A/2x17Ah/LCD power supply for fire alarm systems -
EN54C-10A40LCD - EN54C 27,6V/10A/2x40Ah/LCD power supply for fire alarm systems